Complete
Part No.: 9707278019 (Active Filter Module) Purpose: To verify the electrical integrity and output performance of the AFM, which controls power factor and ...
Wed, 12 Nov, 2025 at 3:01 AM
Power Relay (P/No. 9900262013) Check Point 1: Circuit Connection and Coil Resistance Verify the connection at CN12 on the Control PCB (PWB ASSY). Me...
Wed, 12 Nov, 2025 at 3:03 AM
Part No.: 9705256026 (Filter PCB) Purpose: To verify correct current detection and signal transmission from the Current Transformer (CT) to the Controller ...
Wed, 12 Nov, 2025 at 3:04 AM
Parts: 4-Way Valve: P/No. 9970035012 Solenoid Coil: P/No. 9900191016 Check Point 1: Circuit Connection Confirm correct wiring between connecto...
Wed, 12 Nov, 2025 at 3:06 AM
This procedure outlines how to verify the condition of the indoor fan motor for various ducted models by measuring coil resistance at 20°C. Each fan motor ...
Wed, 12 Nov, 2025 at 8:41 PM
This procedure is used to verify the electrical integrity of fan motors in wall-mounted indoor units by measuring winding resistance at 20°C. Check Point...
Wed, 12 Nov, 2025 at 9:21 PM
This section outlines the DIP switch functions and factory default settings for both wired and simple remote controllers used with J-Series systems. Wired...
Wed, 12 Nov, 2025 at 9:22 PM
This section details the DIP switch functions and factory default settings for the Group Remote Controller, used to control multiple indoor units simultaneo...
Wed, 12 Nov, 2025 at 9:24 PM
This controller allows for external contact signal operation such as remote ON/OFF, mode switching, and parameter control for J-Series systems. DIP Switch...
Wed, 12 Nov, 2025 at 9:27 PM