This document covers the specifications for the indoor model ARTH54KMTAP.

Electrical Data
The unit operates on 220–240 V ~ 50 Hz, with an available voltage range of 198–264 V.

Cooling Performance
Cooling capacity is 13.0 kW (44,400 Btu/h) with a 4.5–15.0 kW capacity range. Rated cooling input power is 4.31 kW (maximum 5.19 kW) and rated cooling current is 18.1 A.

Heating Performance
Heating capacity is 15.1 kW (51,500 Btu/h) with a 4.0–18.0 kW capacity range. Rated heating input power is 4.45 kW (maximum 5.23 kW) and rated heating current is 18.7 A.

Efficiency and Performance Indices
Cooling EER is 3.02 kW/kW and heating COP is 3.37 kW/kW. Maximum operating current is 28.5 A, moisture removal is 5.0 L/h (8.8 pints/h), and power factor is 99.2% (cooling) and 99.2% (heating). Seasonal indices are TCSPF 4.66 / 4.84 / 5.22 (hot/average/cool climate) and HSPF 4.06 / 3.93 / 3.34 (hot/average/cool climate).

Fan, Airflow, and Static Pressure
The fan arrangement is Sirocco fan ×3 with motor output 307 W. Airflow is 2,150 / 1,930 / 1,710 / 1,530 m³/h (cooling) and the same set for heating. Static pressure range is 50–150 Pa.

Noise Level
Sound pressure levels are 40 / 36 / 33 / 29 dB(A) (cooling and heating). Sound power level is 67 dB(A).

Dimensions, Connections, and Controls
Heat exchanger dimensions are 336 × 1,150 × 39.9 mm. Unit dimensions are 240 × 1,400 × 700 mm (net) and 334 × 1,225 × 863 mm (gross), with weight 42 kg net / 48 kg gross. Connection piping is Ø9.52 / Ø15.88 (flare), operating range is 18–32°C cooling (≤80%RH) and 16–30°C heating, controller is wired, and protection rating is IPX0.

Safety Devices
Circuit protection is via PCB fuse (250 V, 5 A). Fan motor thermal protection activates at 110±10°C (fan stop) and resets at 70°C (fan restart).