UTY-CDRXZC and UTY-CDRXZD Temperature Sensor Function Settings

Enabling wired-controller and optional zone temperature sensors
Applicable to the 2-wire Zone Control Interface using UTY-CDRXZC or UTY-CDRXZD wired controllers
Before completing Zone Initial Setting, program the required Zone Function Settings and Indoor Unit Function Setting. These settings enable the primary and secondary wired-controller sensors and up to eight optional remote temperature sensors.
Important: Complete these function settings before Zone Initial Setting and system operation. Confirm all sensor wiring and connections before programming.

1. Required function settings

Zone Controller settings

Use the following Zone Function Settings to enable the required temperature sensors.

Function No.Setting No.Sensor enabledPurpose
0701Primary wired remote controllerEnables the temperature sensor in the primary wall controller.
0801Secondary wired remote controllerEnables the temperature sensor in the secondary wall controller.
31-3801Optional sensors 1-8Enables each connected optional remote sensor individually.

Optional sensor mapping

Function No.Optional sensorEnable setting
31Sensor 101
32Sensor 201
33Sensor 301
34Sensor 401
35Sensor 501
36Sensor 601
37Sensor 701
38Sensor 801

Indoor Unit setting

Function No.Setting No.Description
4201Sets room-temperature sensor switching to Both, allowing the indoor-unit sensor and wired remote-controller temperature sensor to be active.

2. Setting procedure

Step 1 - Open Zone Function Setting

  1. From the main screen, touch Menu.
  2. Touch Next Page until Maintenance is displayed.
  3. Touch Maintenance.
  4. Move through the Maintenance pages and select Zone Function Setting.

Step 2 - Enable the Zone Controller sensors

  1. Touch Function No., select 07, then touch OK.
  2. Touch Setting No., select 01, then touch OK.
  3. Repeat the process for Function 08 when a secondary wired-controller sensor is installed.
  4. For each connected optional sensor, select the applicable Function No. from 31 to 38 and set it to 01.

Step 3 - Set Indoor Unit Function 42

  1. Touch Back to leave Zone Function Setting.
  2. Return to the Maintenance screen and select Function Setting.
  3. Select the applicable indoor-unit address.
  4. Select Function No. 42.
  5. Set the value to 01 and confirm with OK.
Programming sequence: Configure the Zone Function Settings first, then configure Indoor Unit Function 42. Complete Zone Initial Setting only after the required sensor functions have been enabled.

3. Verify active sensors

After programming, confirm that the intended sensors appear in the controller's Priority Sensor list.

  1. From the controller home screen, touch Zone.
  2. Touch Priority Sensor.
  3. Review the displayed sensor numbers and confirm the required sensors are active.
Sensor numberSensor description
1Indoor unit sensor
2Primary wired remote controller
3Secondary wired remote controller
4-11Optional sensors 1-8
Fail-safe display: Sensor 1, the indoor-unit sensor, remains visible in the Priority Sensor list regardless of whether it is selected for normal control. It is retained as a fail-safe if the other sensors become unavailable.

4. Example configuration

For a system using the primary wired-controller sensor and one optional remote sensor:

SettingFunction No.Setting No.Result
Primary WRC sensor0701Primary controller sensor enabled
Optional sensor 13101Optional sensor 1 enabled
Room-temperature sensor switching4201Indoor unit and wired remote-controller sensors active

5. Important service notes

  • Perform all required function settings before Zone Initial Setting.
  • Only enable optional sensors that are physically installed and correctly wired.
  • Confirm the correct indoor-unit address before changing Function 42.
  • Clearly identify each optional sensor and its assigned zone in the commissioning documentation.
  • After programming, use the Priority Sensor screen to confirm the controller has registered the intended sensors.
  • If a sensor does not appear, recheck its wiring, connection, applicable Zone Function number and setting value before repeating Zone Initial Setting.
Technical reference: The controller navigation and function values in this article are based on the UTY-CDRXZC / UTY-CDRXZD 2-wire Zone Control Interface function-setting instructions. Always refer to the latest installation documentation for the connected indoor unit and controls.