Overview

The Fujitsu Airstage AOTA72LALT and AOTA90LALT outdoor units feature a built-in diagnostic and configuration interface, allowing field technicians to monitor operating parameters, adjust function settings, and review system error history without the need for additional tools.
These settings are accessed via the control PCB interface using the Mode, Select, and Enter buttons and the 7-segment LED display.


1. Control Interface Layout

Panel Components

ComponentLabelFunction
POWER/MODE LEDLED101 (Green)Illuminates when powered on
ERROR LEDLED102 (Red)Flashes rapidly to indicate an active fault
7-Segment DisplayLED104 / LED105Displays codes, settings, and modes
MODE / EXIT ButtonSW107Switches between operating and setup modes
SELECT ButtonSW108Scrolls through mode or item numbers
ENTER ButtonSW109Confirms and stores settings
PUMP DOWN / DIP SwitchesSW102 / DIPNot used for normal function setup

2. Normal Operation Indications

Mode DisplayCodeDescription
CLCoolingCooling mode operation
HtHeatingHeating mode operation
dFDefrostDefrost cycle active
PCPower savingReduced capacity operation
LnLow noiseQuiet outdoor operation active
StoppedUnit idle or off

3. Function Modes Overview

Available Modes and Settings

ClassificationMode CodeFunctionItem No.DescriptionDefault
Monitor Mode[F1]System data view10–51View compressor speed, fan RPM, pressures, thermistors, and EEV pulse
Setting Mode[F2]Functional adjustments00–42Adjust installation, correction, and operation parametersFactory defaults
Function Mode[F3]Service & reset functions00–31Perform test run, forced operation, or clear stored data
Error History[F9]Fault review00–03Displays last 4 logged errors with timestamp

4. Key Function Settings – [F2] Mode

Setting FunctionItem No.Options / DescriptionDefault
Pipe Length Setting0000 = 40–65m, 01 = 65–90m00
Defrost Shift 11300 = Normal, 01 = Hotter end temp, 02 = Cooler end temp00
Defrost Shift 22000 = Normal start, 01 = Longer start, 02 = Shorter start00
Energy Saving Mode3000 = Off, 01 = 75% capacity, 02 = 50% capacity00
Low Noise Mode4100 = Normal, 01 = Level 1, 02 = Level 200
Low Noise Operation Level4200 = Off, 01 = 3 dB reduction, 02 = 6 dB reduction, 03 = 9 dB reduction00

5. Function Mode – [F3]

Used primarily for testing, commissioning, and clearing data.

Item No.FunctionDescription
00Cooling Test RunForced ON cooling operation
01Heating Test RunForced ON heating operation
02Stop Test RunTerminates forced operation
30Error History ClearClears all stored fault logs
33Compressor Run Time ClearResets inverter compressor accumulated time
50Field Setting ResetRestores all values to factory defaults

6. Error History Mode – [F9]

Displays recent system faults for diagnostics.

Item No.Display MeaningDescription
00Latest ErrorMost recent fault event
01One Error AgoPrevious error
02Two Errors AgoSecond previous fault
03Three Errors AgoThird previous fault
04Four Errors AgoFourth previous fault

Use this mode to cross-reference fault patterns with LED codes during troubleshooting.


7. Field Service Tips

  • To enter function mode, press MODE/EXIT repeatedly until the desired function (e.g., F1, F2, F3, F9) appears, then press ENTER.

  • Use SELECT to choose the item number and ENTER to confirm.

  • To exit, press MODE/EXIT until the normal display reappears.

  • Always record any modified parameters in the service log for traceability.