General Assist Technical Reference

ARTG54LHTC & AOTG54LCTL

Ducted inverter heat pump — specifications, installation limits and controls
Indoor unit: ARTG54LHTC  |  Outdoor unit: AOTG54LCTL  |  Refrigerant: R410A
Quick answer: This matched ducted system is rated at 14.0 kW cooling and 16.0 kW heating. Standard pipe sizes are 9.52 mm (3/8 in.) liquid and 15.88 mm (5/8 in.) gas. The outdoor unit is factory charged with 3.45 kg of R410A for up to 30 m of standard-size piping.

1. Quick specifications

System typeDucted inverter heat pump
Indoor unitARTG54LHTC
Outdoor unitAOTG54LCTL
Power supply1 phase, 240 V AC, 50 Hz
Available voltage range198–264 V
Cooling capacity14.0 kW rated  |  6.2–15.2 kW range
Heating capacity16.0 kW rated  |  6.2–18.0 kW range
Rated inputCooling 4.40 kW  |  Heating 4.37 kW
EfficiencyEER 3.18  |  COP 3.66
Maximum operating current23.5 A — total system
RefrigerantR410A

Unit dimensions and weight

UnitDimensions (H × W × D)Net weight
ARTG54LHTC indoor425 × 1,250 × 490 mm54 kg
AOTG54LCTL outdoor1,290 × 900 × 330 mm93 kg

2. Indoor airflow and static pressure

Fan settingAirflowSound pressure
High986 L/s (3,550 m³/h)45 dB(A)
Medium833 L/s (3,000 m³/h)40 dB(A)
Low681 L/s (2,450 m³/h)36 dB(A)
Static pressure: Recommended operating range is 60–260 Pa. The factory function setting is 60 Pa.
Function 21 settingStatic pressure
00 — Normal60 Pa
02 — Static pressure 1100 Pa
03 — Static pressure 2150 Pa
04 — Static pressure 3200 Pa
05 — Static pressure 4250 Pa

3. Refrigerant pipework and charge

Standard liquid pipe9.52 mm (3/8 in.)
Standard gas pipe15.88 mm (5/8 in.)
Factory refrigerant charge3,450 g R410A
Pre-charge length30 m with standard 3/8 in. liquid + 5/8 in. gas pipe
Maximum pipe length75 m with standard pipe sizes
Maximum height difference30 m
Additional charge — standard pipe sizes50 g/m for piping beyond 30 m
Important: Different maximum lengths and refrigerant charge rates apply if pipe sizes are changed. Use the pipe-size selection and additional-charge tables in the technical manual before altering the standard 3/8 in. liquid and 5/8 in. gas sizes.

Capacity reduction with long pipework

System capacity reduces as pipe length and height difference increase. As an example, at 75 m pipe length and zero height difference, the manual gives a cooling compensation factor of 0.753 and a heating compensation factor of 0.935.

4. Electrical requirements

System supply240 V AC, 50 Hz
Maximum system current23.5 A
Circuit breaker30 A
Outdoor power cable6.0 mm² minimum
Indoor maximum operating current3.5 A
Indoor-to-outdoor connection cable1.5 mm² minimum; listed limit 75 m
Electrical work: Cable selection, protection and installation must comply with the applicable local electrical rules. The technical manual notes that conductor size should be increased if voltage drop reaches 2% or more.

5. Controllers and optional parts

PartModelPurpose
Wired remote controllerUTY-RVNYNFull-dot display controller; supports function settings, timers and sensor control.
Wired remote controllerUTY-RNNYNWired controller with weekly/setback timer and built-in temperature sensor.
Simple remote controllerUTY-RSNYNBasic Start/Stop, fan, temperature and mode control.
IR receiver unitUTY-LRHYMInfrared receiver option.
Zone control interfaceUTY-CDPXZC / UTY-CDPXZDControls individual zone airflow by operating supply-air dampers.
Remote sensorUTY-XSZXRemote room temperature sensing.
Indoor external control setUTD-ECS5AConnection leads for indoor external input/output functions.
Outdoor external connect kitUTY-XWZXZ3Required for outdoor low-noise, peak-cut and status I/O.

Dual wired remote controllers

Two wired remote controllers can be connected for local and remote control. One controller must be configured as Primary/Master and the second as Secondary/Slave. Timer functionality on the secondary controller is restricted.

Indoor external input / output

FunctionConnector
Control input — Operation/Stop or Forced StopCN103
Operation status outputCN100
Error status outputCN101
Fresh-air control outputCN161
Auxiliary heater outputCN160

Outdoor external input / output

FunctionConnector
Low noise mode inputCN10
Peak cut mode inputCN11
Error status outputCN12
Compressor status outputCN13
Low noise mode: Level 1 reduces rated outdoor sound by approximately 2 dB and Level 2 by approximately 4 dB. Performance may reduce while low noise mode is active.
Peak cut: Outdoor peak-cut settings are provided for approximately 0%, 50%, 75% or 100% of rated input. Restricting input can reduce available capacity.

6. Common indoor function settings

FunctionNo.Key settings
Filter sign interval1100 = 2,500 h; 01 = 5,000 h; 02 = 1,250 h; 03 = no indication
Static pressure2100 = 60 Pa; 02 = 100 Pa; 03 = 150 Pa; 04 = 200 Pa; 05 = 250 Pa
Cooling room-temp correction3000 standard; 01 higher; 02 slightly higher; 03 slightly lower; 04 lower
Heating room-temp correction3100 standard; 01 higher; 02 slightly higher; 03 slightly lower; 04 lower
Auto restart4000 enable; 01 disable
Room sensor switching4200 indoor unit; 01 both indoor and wired controller sensors
Cold air prevention4300 enable; 01 disable
External input control4600 Operation/Stop; 02 Forced Stop
Room sensor switching — auxiliary4800 both; 01 wired remote controller only. Function 42 must first be set to 01.
After changing indoor function settings: Turn the power off, wait at least 30 seconds, then turn it back on. The manual states that the new function setting will not become active until this power cycle is completed.

Fan delay for auxiliary heater

Jumper JM42 controls the one-minute indoor fan delay after the unit stops while operating with an auxiliary heater. Factory condition is connected = delay invalid; disconnecting JM42 enables the one-minute fan delay.

7. Installation and operating limits

Indoor unit service space

  • Top-service arrangement: approximately 350 mm or more above the unit and 500 mm or more service access.
  • Bottom-service arrangement: 20 mm or more above the unit and 500 mm or more service access below.
  • Keep wiring, lighting and other obstructions out of the designated service space.

Outdoor unit operating range

ModeOutdoor temperature range
Cooling-15 °C to 46 °C
Heating-15 °C to 24 °C

Typical outdoor clearances — single unit, open above

ObstructionMinimum clearance shown in manual
Rear only150 mm
Rear and sidesRear 200 mm; sides 200 mm / 300 mm as shown
Front only1,000 mm or more
Front and rearFront 1,000 mm or more; rear 150 mm
Installation note: Different clearances apply where there are overhead obstructions, multiple outdoor units or multi-row installations. Refer to the installation diagrams in the technical manual for the exact arrangement.

8. Reference conditions

Published ratings are based on 7.5 m pipe length, zero height difference and, for the indoor unit, 60 Pa standard static pressure. Rated cooling conditions are indoor 27 °C DB / 19 °C WB and outdoor 35 °C DB / 24 °C WB. Rated heating conditions are indoor 20 °C DB / 15 °C WB and outdoor 7 °C DB / 6 °C WB.

Technical information based on Design & Technical Manual DTR_AR056E_04 for ARTG54LHTC / AOTG54LCTL. Verify installation requirements against the applicable installation manual and local regulations before carrying out work.