Overview

It has been identified that, in some cases, the factory-supplied wire harness included with UTY-CDPXZC and UTY-CDPXZD Zone Modules may have incorrect polarity when connecting to CN6 on the zone module’s main PCB.

This article outlines how to identify the incorrect harness and ensure the correct wiring connection is made.


1. Affected Models

  • UTY-CDPXZC Zone Module

  • UTY-CDPXZD Zone Module


2. Issue Description

During installation, some units have been supplied with a reversed-polarity wire harness for the CN6 connector.
If connected incorrectly, this can cause communication errors or failure of the zone control function.

Harness IdentificationStatusDescription
Blue Dot Harness (Left)IncorrectFactory harness wired with reversed polarity – must not be used.
Green Dot Harness (Right)CorrectProper polarity – safe to connect to CN6 on the zone module.

3. Correct Connection Reference

  • Ensure the harness with a green identification dot is used when connecting to CN6.

  • If only the blue-dot harness is available, do not install — contact Fujitsu General Technical Support for a replacement.

  • The CN6 connector is located on the lower right section of the Zone Module PCB.





4. Symptoms of Incorrect Harness Installation

If the incorrect (blue dot) harness is connected:

  • The zone controller will not operate correctly.

  • Communication fault codes may be displayed.

  • The LED indicators on the module may not illuminate or blink as expected.


5. Corrective Action

  1. Inspect the harness supplied with the Zone Module before installation.

  2. Confirm the colour dot marking on the harness plug:

    • Use only the Green Dot harness.

    • Discard or return any Blue Dot harnesses.

  3. Reconnect the correct harness to CN6 on the Zone Module PCB.

  4. Power cycle the unit and confirm communication and zone operation.


The correct combination is;

Pin 1 = Red

Pin 2 = White

Pin 3 = Black

Pin 4 = NA

Pin 5 = NA


6. Visual Reference

Incorrect HarnessCorrect Harness
Blue DotGreen Dot

⚠️ Important: The Blue Dot harness must not be used under any circumstances, as reversed polarity may cause module malfunction or damage.