VII and VIII Test Run, Error Reset and Central Controller Release

Purpose: Use the outdoor unit PCB push-button switches to start a cooling or heating test run, stop a test run, reset errors, or release a central control forced-reset condition.

Outdoor PCB controls

ItemReferenceFunction
MODE / EXITSW107Moves between monitoring, mode selection and exit/return screens.
SELECTSW108Scrolls through available modes and functions.
ENTERSW109Confirms the selected mode or executes the selected function.
7-segment displayLED105 / LED104Displays the current mode, function number and completion indication.
Important: The procedure is performed at the outdoor unit printed circuit board. Only suitably qualified service personnel should access or operate controls inside the electrical enclosure.

Entering Function Mode

  1. From the normal monitoring condition, press MODE / EXIT (SW107) to enter the mode-select condition.
  2. Press SELECT (SW108) until the 7-segment display shows F3 for Function mode.
  3. Press ENTER (SW109) to enter the function-select condition.
Navigation summary:
Monitoring condition → MODE/EXIT → SELECT to F3 → ENTER → select the required function.

Function selections

DisplayFunctionAction
01Cooling test runSelect 01, then hold ENTER (SW109) for at least 3 seconds.
02Heating test runSelect 02, then hold ENTER (SW109) for at least 3 seconds.
03Test run stopSelect 03, then hold ENTER (SW109) for at least 3 seconds.
04Error resetSelect 04, then hold ENTER (SW109) for at least 3 seconds.
91Central control setting forced resetSelect 91, then hold ENTER (SW109) for at least 3 seconds to release the central-control forced setting.

Completing the command

  1. Use SELECT (SW108) to choose the required function number.
  2. Hold ENTER (SW109) for at least 3 seconds.
  3. The display indicates that the command has been carried out. Press ENTER (SW109) again, or wait approximately 5 seconds, to return to the mode-select condition.
  4. Press MODE / EXIT (SW107) to return to the normal monitoring condition.

Quick procedure

For cooling test run, heating test run, stop or error reset
MODE/EXITSELECT to F3ENTERSELECT 01 / 02 / 03 / 04 → hold ENTER for 3+ secondsENTER or wait 5 secondsMODE/EXIT.
For central controller release / forced reset
MODE/EXITSELECT to F3ENTERSELECT 91 → hold ENTER for 3+ secondsENTER or wait 5 secondsMODE/EXIT.
Normal indication: After returning to the monitoring condition, the display returns to the normal operating/monitoring indication. The example shown in the source material is cooling mode.