VRF VII - Compressor Operation and Control
1. Compressor Operation / Stop Conditions
When either cooling requirement capacity or heating requirement capacity is received from an indoor unit within the same refrigerant circuit, the compressor operates.
When all indoor units have a cooling requirement capacity or heating requirement capacity of 0, the compressor is stopped.
The compressor may still operate during the following control conditions:
- 3-minute restart prevention operation
- Icing protection
- Failure / protection operation
- Oil recovery
- Electronic expansion valve initialisation
- Protective operation
- Emergency stop processing
- Defrost operation
- Peak cut stop operation
2. Capacity Control
By combining operation of the DC inverter rotary compressor and constant-speed scroll compressors, the system supplies the required refrigerant circulation according to the cooling or heating load.
The inverter compressor provides fine capacity control by varying rotational speed. As system load increases, additional compressor capacity is staged in.
Target Low-Pressure and High-Pressure Control
Cooling: compressor capacity is controlled using the outdoor-unit low-pressure sensor so that indoor-unit evaporation pressure is maintained at the required level.
Heating: compressor capacity is controlled using the outdoor-unit high-pressure sensor so that indoor-unit condensing pressure is maintained at the required level.
3. Inverter Compressor Speed Range
| Condition | Speed |
|---|---|
| Stop mode | 0 rps |
| Operating mode | 30 - 100 rps |
| Multiple outdoor unit system | Master and slave inverter compressors are controlled at the same rotational speed. |
Cooling Starting Process
For cooling operation, the upper compressor speed limit at start-up is 50 rps and is increased in 10 rps increments every 60 seconds.
| Elapsed Time | Upper Limit |
|---|---|
| Start | 50 rps |
| 60 sec | 60 rps |
| 120 sec | 70 rps |
| 180 sec | 80 rps |
| 240 sec | 90 rps |
- If target speed is higher than the current upper limit, the compressor operates at the upper limit.
- If target speed is lower than the current upper limit, the compressor operates at target speed.
Heating Starting Process
At the start of heating, all compressor start-up operation is controlled in association with four-way valve changeover. Normal target high-pressure control resumes after the starting process is complete.
| Outdoor Unit | Starting Process 1 | Starting Process 2 |
|---|---|---|
| O2 compressor 12, 14, 16 HP | 30 rps fixed, with constant-speed compressor ON | 70 rps fixed |
| O1 compressor 8, 10 HP | 70 rps fixed | 70 rps fixed |
Starting Process 1 ends when:
- 7 minutes have elapsed, or
- 1 minute has elapsed and high pressure of all outdoor units is at least 2.50 MPa, or
- Compression ratio of any outdoor unit exceeds 8.
Starting Process 2 ends when:
- 30 minutes have elapsed, or
- High pressure of all outdoor units is at least 2.63 MPa, or
- Discharge superheat of all operating compressors exceeds 12°C.
A. Outside air temperature is above 20°C, or
B. The heating starting process, including thermostat-OFF stop, has occurred within the previous 30 minutes.
When these conditions apply, the inverter compressor of all outdoor units starts at 40 rps and normal target high-pressure control begins immediately.
High-Pressure Speed Limiting
| High Pressure | Maximum Speed |
|---|---|
| Below calculated threshold [a] | 100 rps |
| Approx. 3.00 MPa | 95 rps |
| Approx. 3.30 MPa | 90 rps |
| Approx. 3.80 MPa | 80 rps |
4. Compressor Sequence Operation
The system creates a starting sequence and starts and stops compressors according to that sequence.
- Starting sequence 1: compressor starts first and stops last.
- Starting sequence 2: compressor starts second and stops second from the end.
- Inverter compressors are started before constant-speed compressors.
- Operating inverter compressors are controlled to the same speed where possible, subject to upper and lower speed limits.
Starting Sequence Rotation
The compressor starting sequence is rotated during:
- Defrosting
- Oil recovery
- High cooling discharge temperature
5. Key Diagnostic Points
- A compressor not operating does not automatically indicate a fault; first confirm current system load and sequence.
- Cooling start-up intentionally limits inverter speed for the first several minutes.
- Heating start-up can hold compressor speed at fixed values while target high pressure is established.
- Rising high pressure can intentionally reduce maximum inverter speed.
- Defrost and oil recovery can change normal compressor sequence.
- In multi-outdoor systems, inverter compressors are normally controlled at the same rotational speed.