General Assist Technical Reference
J-IIIL Outdoor Unit Wiring Diagram
Electrical wiring and connector reference
Applicable models: AJ*040LELAH, AJ*045LELAH, AJ*054LELAH
Electrical safety: This reference includes 3-phase 400 V power circuits and inverter components. Isolate the outdoor unit, verify the supply is dead and allow the inverter DC bus to discharge before accessing electrical components.
Use this article as a quick wiring and connector reference. The original wiring diagram remains the controlling document when tracing individual conductors or terminal positions.
1. Applicable models
| Series | Models shown on wiring diagram |
|---|---|
| J-IIIL | AJ*040LELAH / AJ*045LELAH / AJ*054LELAH |
2. Power supply, noise filter and inverter circuit
| Item | Diagram reference | Notes |
|---|---|---|
| Incoming supply | Terminal L1 / L2 / L3 / N + Earth | 3N~ 50 Hz, 400 V shown on the source diagram. |
| Noise-filter board | F501, F503 | Both fuses are shown as 5 A / 250 V. |
| Inverter board | CN801 / CN802 and associated terminals | Feeds the three-phase compressor motor and interfaces with the control board. |
| Compressor | Motor (compressor) MS 3~ | R / S / C motor conductors are shown at the inverter output. |
| Reactor | TM812 / TM814 | Located in the inverter power circuit. |
3. Outdoor components and connectors
| Component | Connector / reference | Wiring shown |
|---|---|---|
| High pressure sensor | CN118 | Red / White / Black |
| Low pressure sensor | CN119 | Red / White / Black |
| Pressure switch | CN120 | Blue / Blue |
| Solenoid coil 2 | CN107 | Blue / Blue |
| 4-way valve coil | CN105 | Blue / Blue |
| Crankcase heater | CN113 | Black / Black |
| Expansion valve coil 1 | CN116 | 6-wire stepper-motor connection |
| Expansion valve coil 2 | CN117 | 6-wire stepper-motor connection |
| Fan motor 1 - upper | CN102 | Red / Black / White / Yellow / Blue / Brown |
| Fan motor 2 - lower | CN150 | Red / Black / White / Yellow / Blue / Brown |
4. Thermistor connections
| Thermistor | Function | Harness marking |
|---|---|---|
| TH1 | Discharge temperature | Blue |
| TH10 | Compressor shell temperature | - |
| TH7 | Sub-cool heat exchanger inlet - liquid | Green |
| TH8 | Sub-cool heat exchanger inlet - gas | White |
| TH9 | Sub-cool heat exchanger exit - gas | Brown |
| TH4 | Suction temperature | Red |
| TH5 | Heat exchanger exit temperature | Pink |
| TH3 | Outdoor temperature | - |
Harness identification: The source diagram includes a thermistor marking table. Where a harness colour is listed above, use the harness marking together with the connector location and sensor function to confirm identification.
5. External connections
| Connection | Reference | Purpose shown |
|---|---|---|
| External output 1 | CN136 | External output |
| External output 2 | CN137 | External output |
| Pulse input | CN135 | Pulse input |
| External input 1 | CN131 | EXT. IN.1 |
| External input 2 | CN132 | EXT. IN.2 |
| External input 3 | CN133 | EXT. IN.3 |
| External input 4 | CN134 | EXT. IN.4 |
| Indoor / other cycle communication | Terminal CN101 | X1 / X2 and Z1 / Z2 communication terminals are shown. |
6. Technician wiring-trace procedure
- Confirm the exact outdoor model matches the models listed in this article.
- Isolate the unit and verify the incoming supply is dead before removing electrical covers.
- Identify the component and its connector number from the tables above.
- Trace the harness using connector number, wire colour and terminal position together. Do not identify a circuit from wire colour alone.
- Check connectors for poor seating, corrosion, heat damage, damaged locking tabs, loose terminals or harness damage.
- Where a sensor or actuator is being electrically tested, use the applicable service procedure for the required resistance or voltage specification. Those test values are not provided on this wiring diagram.
- After repairs, refit all covers and confirm normal operation.
Important: This wiring diagram identifies circuit routing and connector locations. It does not provide component resistance values, operating voltages, fault thresholds or live-test procedures. Use the relevant service manual test procedure before condemning a PCB, sensor, motor, valve or compressor.
Source reference: J-IIIL Wiring Diagram, page 05-20.