General Assist Technical Reference

AIRSTAGE V-II Series VRF

System introduction and compatible indoor-unit lineup
Approximate product era: early to mid-2010s
The AIRSTAGE V-II Series is a large-capacity R410A VRF platform developed as the successor to the original V Series. It was designed for multi-storey offices, hotels, education, healthcare, retail and other large commercial applications requiring extensive zoning and centralised control.
Naming caution: “V-II” may be written informally as “VII,” but it is not the same as the later V-III generation. Always confirm the complete model number before selecting manuals, PCBs, controllers, indoor units or commissioning procedures.

1. Key technical highlights

FeatureTypical V-II Series reference
RefrigerantR410A
System typeHeat pump and heat-recovery VRF configurations, model dependent
Compressor technologyDC inverter scroll compressor control, with multiple-compressor and rotation logic on applicable modules
Outdoor capacityApproximately 22 kW upward, with modular combinations for larger systems
Indoor-unit connectionsUp to 48 indoor units on applicable system combinations
Total piping lengthUp to approximately 1,000 m on applicable system configurations
Height differenceUp to approximately 110 m where the specific design conditions allow
ControlsWired controllers, central controllers, touch panels and BMS interfaces
Approximate eraCirca 2012–2016, varying by market and model
The maximum piping, height and indoor-unit figures depend on the exact outdoor combination and design conditions. Do not apply headline maximums to every system without checking the applicable design and installation manual.

2. Indoor-unit lineup

The uploaded two-page lineup shows indoor units from approximately 2.2 kW to 28.0 kW cooling capacity, covering cassette, concealed duct, floor/ceiling, ceiling and wall-mounted configurations.

Cassette indoor units

TypeModels shownCooling rangeAccessory
Compact cassetteAUXB07GALH, AUXB09GALH, AUXB12GALH, AUXB14GALH, AUXB18GALH, AUXB24GALH2.2–7.1 kWUTG-UFYC-W grille
CassetteAUXD18GALH, AUXD24GALH, AUXA18GALH, AUXA24GALH, AUXA30GALH, AUXA34GALH, AUXA36GALH, AUXA45GALH, AUXA54GALH5.6–14.0 kWUTG-UGYA-W grille

Ducted and concealed indoor units

TypeModels shownCooling range
Low-static / concealed floorARXB07GALH, ARXB09GALH, ARXB12GALH, ARXB14GALH, ARXB18GALH2.2–5.6 kW
Compact slim ductARXK07GCLH / GALH through ARXK24GCLH / GALH2.2–7.1 kW
Slim duct / slim concealed floorARXD07GALH, ARXD09GALH, ARXD12GALH, ARXD14GALH, ARXD18GALH, ARXD24GALH2.2–7.1 kW
Low-static pressure ductARXB24GALH, ARXB30GALH, ARXB36GALH, ARXB45GALH7.1–12.5 kW
Medium-static pressure ductARXA24–45GALH and ARXA24–45GBLH7.1–12.5 kW
High-static pressure ductARXC36GATH, ARXC36GBTH, ARXC45GATH, ARXC60GATH, ARXC72GATH, ARXC90GATH, ARXC96GATH11.2–28.0 kW

Floor, ceiling and wall-mounted indoor units

TypeModels shownCooling rangeNotes
Floor / ceilingABYA12GATH, ABYA14GATH, ABYA18GATH, ABYA24GATH3.6–7.1 kWConvertible floor or ceiling installation
CeilingABYA30GATH, ABYA36GATH, ABYA45GATH, ABYA54GATH9.0–14.0 kWCeiling-suspended type
Wall mountedASYA07GACH, ASYA09GACH, ASYA12GACH, ASYA14GACH, ASYA18GACH, ASYA24GACH, ASYA30GACH2.2–8.0 kWStandard internal EEV models
Wall mounted with external EEVASYE07GACH, ASYE09GACH, ASYE12GACH, ASYE14GACH2.2–4.5 kWUTR-EV09XB or UTR-EV14XB required

External EEV kit reference

Indoor capacity classEEV kit
07 / 09 classUTR-EV09XB
12 / 14 classUTR-EV14XB

3. Service and replacement guidance

1Confirm the generation.
V-II components, controls and addressing procedures must not be assumed interchangeable with V Series, V-III, VR-II, VR-III or J Series equipment.
2Use the complete model number.
Suffixes such as GALH, GBLH, GATH, GBTH and GACH identify different product arrangements and must be matched exactly.
3Verify spare-parts availability.
Production has ceased and availability varies by part. Confirm stock and supersession before committing to repair.
4Readdress replacement PCBs.
When replacing indoor or outdoor control boards, transfer DIP-switch settings and complete the applicable addressing and capacity-check process.
5Plan replacement carefully.
Existing R410A pipework and controls require engineering assessment before reuse with a newer VRF platform.
Escalation information: Provide outdoor and indoor model numbers, serial numbers, controller type, refrigerant-system address, indoor-unit address, fault history, LED display, PCB part numbers and details of any recent component replacement.
Do not mix generations: A physical or electrical connector appearing similar does not establish compatibility. Use the V-II design, installation and service documentation for all selections and repairs.
This article is a practical overview based on the supplied V-II Series indoor-unit lineup. It does not replace the applicable design, installation, service or commissioning manuals. Maximum system values vary by outdoor model, combination and design conditions.