General Assist Technical Reference

J-II Indoor Unit Line-up & Connection Capacity

Outdoor unit capacities, maximum indoor unit quantities and compatible J-II indoor unit models
Use this reference when selecting indoor units for a J-II refrigerant system. Confirm the outdoor unit model, maximum number of connectable indoor units and total connectable indoor-unit capacity before finalising the combination.

1. J-II outdoor unit line-up

HPCooling CapacityHeating CapacityOutdoor ModelMax. Indoor UnitsConnectable Indoor Capacity
411.2 kW12.5 kWAJYA36LALH65.6 to 14.5 kW
514.0 kW16.0 kWAJYA45LALH87.0 to 18.2 kW
615.5 kW18.0 kWAJYA54LALH97.8 to 20.1 kW
Important: The total connected indoor-unit rated capacity must remain within the connectable capacity range shown for the selected outdoor unit. The maximum indoor-unit quantity must also not be exceeded.

2. Compatible indoor unit line-up

Compact Cassette

CoolingHeatingModelDimensions H x W x DRemarks
2.2 kW2.8 kWAUXB07GALH245 x 570 x 570 mmCassette grille: UTG-UFYC-W
2.8 kW3.2 kWAUXB09GALH
3.6 kW4.1 kWAUXB12GALH
4.5 kW5.0 kWAUXB14GALH
5.6 kW6.3 kWAUXB18GALH
7.1 kW8.0 kWAUXB24GALH

Cassette

CoolingHeatingModelDimensions H x W x DRemarks
5.6 kW6.3 kWAUXD18GALH246 x 840 x 840 mmCassette grille: UTG-UGYA-W
7.1 kW8.0 kWAUXD24GALH246 x 840 x 840 mm
5.6 kW6.3 kWAUXA18GALH288 x 840 x 840 mm
7.1 kW8.0 kWAUXA24GALH
9.0 kW10.0 kWAUXA30GALH
10.0 kW11.2 kWAUXA34GALH
11.2 kW12.5 kWAUXA36GALH
12.5 kW14.0 kWAUXA45GALH288 x 840 x 840 mmGrille as above
14.0 kW16.0 kWAUXA54GALH288 x 840 x 840 mmGrille as above

Circular Flow Cassette

CoolingHeatingModelDimensions H x W x DRemarks
5.6 kW6.3 kWAUXM018GLAH246 x 840 x 840 mmCassette grille: UTG-UKYC-W
7.1 kW8.0 kWAUXM024GLAH246 x 840 x 840 mm
9.0 kW10.0 kWAUXM030GLAH288 x 840 x 840 mm
5.6 kW6.3 kWAUXK018GLAH
7.1 kW8.0 kWAUXK024GLAH
9.0 kW10.0 kWAUXK030GLAH
10.0 kW11.2 kWAUXK034GLAH
11.2 kW12.5 kWAUXK036GLAH
12.5 kW14.0 kWAUXK045GLAH288 x 840 x 840 mmGrille as above
14.0 kW16.0 kWAUXK054GLAH288 x 840 x 840 mmGrille as above

Low Static Pressure Duct / Concealed Floor

CoolingHeatingModelDimensions H x W x D
2.2 kW2.8 kWARXB07GALH217 x 663 x 595 mm
2.8 kW3.2 kWARXB09GALH217 x 663 x 595 mm
3.6 kW4.0 kWARXB12GALH217 x 953 x 595 mm
4.5 kW5.0 kWARXB14GALH
5.6 kW6.3 kWARXB18GALH

Mini Duct - With Drain Pump

CoolingHeatingModelDimensions H x W x D
2.2 kW2.8 kWARXK07GCLH198 x 700 x 450 mm
2.8 kW3.2 kWARXK09GCLH198 x 700 x 450 mm
3.6 kW4.0 kWARXK12GCLH198 x 700 x 450 mm
4.5 kW5.0 kWARXK14GCLH198 x 700 x 450 mm
5.6 kW6.3 kWARXK18GCLH198 x 900 x 450 mm
7.1 kW8.0 kWARXK24GCLH198 x 1,100 x 450 mm

Mini Duct - Without Drain Pump

CoolingHeatingModelDimensions H x W x D
2.2 kW2.8 kWARXK07GALH198 x 700 x 450 mm
2.8 kW3.2 kWARXK09GALH198 x 700 x 450 mm
3.6 kW4.0 kWARXK12GALH198 x 700 x 450 mm
4.5 kW5.0 kWARXK14GALH198 x 700 x 450 mm
5.6 kW6.3 kWARXK18GALH198 x 900 x 450 mm
7.1 kW8.0 kWARXK24GALH198 x 1,100 x 450 mm

Slim Duct / Slim Concealed Floor

CoolingHeatingModelDimensions H x W x D
2.2 kW2.8 kWARXD07GALH198 x 700 x 620 mm
2.8 kW3.2 kWARXD09GALH198 x 700 x 620 mm
3.6 kW4.0 kWARXD12GALH198 x 700 x 620 mm
4.5 kW5.0 kWARXD14GALH198 x 700 x 620 mm
5.6 kW6.3 kWARXD18GALH198 x 900 x 620 mm
7.1 kW8.0 kWARXD24GALH198 x 1,100 x 620 mm

Low Static Pressure Duct

CoolingHeatingModelDimensions H x W x D
7.1 kW8.0 kWARXB24GALH270 x 1,135 x 700 mm
9.0 kW10.0 kWARXB30GALH
11.2 kW12.5 kWARXB36GALH
12.5 kW14.0 kWARXB45GALH

Medium Static Pressure Duct

CoolingHeatingModelDimensions H x W x D
7.1 kW8.0 kWARXA24GALH270 x 1,135 x 700 mm
9.0 kW10.0 kWARXA30GALH
11.2 kW12.5 kWARXA36GALH
12.5 kW14.0 kWARXA45GALH
7.1 kW8.0 kWARXA24GBLH
9.0 kW10.0 kWARXA30GBLH
11.2 kW12.5 kWARXA36GBLH
12.5 kW14.0 kWARXA45GBLH

High Static Pressure Duct

CoolingHeatingModelDimensions H x W x D
11.2 kW12.5 kWARXC36GBTH400 x 1,050 x 500 mm
11.2 kW12.5 kWARXC36GATH
12.5 kW14.0 kWARXC45GATH

Floor / Ceiling

CoolingHeatingModelDimensions H x W x D
3.6 kW4.0 kWABYA12GATH199 x 990 x 655 mm
4.5 kW5.0 kWABYA14GATH
5.6 kW6.3 kWABYA18GATH
7.1 kW8.0 kWABYA24GATH

Ceiling

CoolingHeatingModelDimensions H x W x D
9.0 kW10.0 kWABYA30GATH240 x 1,660 x 700 mm
11.2 kW12.5 kWABYA36GATH
12.5 kW14.0 kWABYA45GATH
14.0 kW16.0 kWABYA54GATH

Compact Floor

CoolingHeatingModelDimensions H x W x D
2.2 kW2.8 kWAGYA007GCAH600 x 740 x 200 mm
2.8 kW3.2 kWAGYA009GCAH
3.6 kW4.0 kWAGYA012GCAH
4.0 kW4.5 kWAGYA014GCAH

Compact Floor - EEV External

CoolingHeatingModelDimensions H x W x DEV Kit
2.2 kW2.8 kWAGYE007GCAH600 x 740 x 200 mmUTR-EV09XB
2.8 kW3.2 kWAGYE009GCAHUTR-EV09XB
3.6 kW4.0 kWAGYE012GCAHUTR-EV14XB
4.0 kW4.5 kWAGYE014GCAHUTR-EV14XB

Wall Mounted

CoolingHeatingModelDimensions H x W x D
2.2 kW2.8 kWASYA07GACH275 x 790 x 215 mm
2.8 kW3.2 kWASYA09GACH
3.6 kW4.1 kWASYA12GACH
4.5 kW5.0 kWASYA14GACH
5.6 kW6.3 kWASYA18GACH320 x 998 x 228 mm
7.1 kW8.0 kWASYA24GACH
8.0 kW9.0 kWASYA30GACH
2.2 kW2.8 kWASYA007GTAH262 x 820 x 206 mm
2.8 kW3.2 kWASYA009GTAH
3.6 kW4.1 kWASYA012GCAH
4.5 kW5.0 kWASYA014GCAH275 x 790 x 215 mm
5.6 kW6.3 kWASYA18GBCH320 x 998 x 238 mm
7.1 kW8.0 kWASYA24GBCH
9.0 kW10.0 kWASYA030GTAH340 x 1,150 x 280 mm
10.0 kW11.2 kWASYA034GTAH

Wall Mounted - EEV External

CoolingHeatingModelDimensions H x W x DEV Kit
2.2 kW2.8 kWASYE07GACH275 x 790 x 215 mmUTR-EV09XB
2.8 kW3.2 kWASYE09GACHUTR-EV09XB
3.6 kW4.1 kWASYE12GACHUTR-EV14XB
4.5 kW5.0 kWASYE14GACHUTR-EV14XB
2.2 kW2.8 kWASYE007GTAH262 x 820 x 206 mmUTR-EV09XB
2.8 kW3.2 kWASYE009GTAH262 x 820 x 206 mmUTR-EV09XB
3.6 kW4.1 kWASYE012GCAH268 x 840 x 203 mmUTR-EV14XB
4.5 kW5.0 kWASYE014GCAH268 x 840 x 203 mmUTR-EV14XB

3. Selection notes

  • Check both the maximum indoor unit quantity and the total connected rated capacity against the selected outdoor unit.
  • For cassette units, confirm the correct grille part number shown in the table.
  • For EEV-external compact-floor and wall-mounted units, the applicable EV kit must be included.
  • Dimensions shown are H x W x D in millimetres.
  • Use the applicable current design/technical and installation documentation when confirming a final project combination.
Source note: This article is based on the J-II model line-up pages supplied. It is intended as a quick selection reference and does not replace project-specific design requirements.