General Assist Technical Reference

J Series Troubleshooting & Error Codes

Indoor, outdoor and controller fault identification and diagnostic checks
Technical reference for J Series systems using receiver LEDs, outdoor PCB LEDs and remote-controller error codes.
How to use this article: Identify the fault from the indoor receiver, wired controller or outdoor PCB first. Then use the matching troubleshooting section below. Outdoor faults are commonly shown as E:32 at the indoor controller, so the outdoor PCB LED pattern is required to identify the specific outdoor fault.
Qualified service personnel only: These checks include live electrical measurements, refrigerant-system diagnosis and high-pressure components. Isolate power before disconnecting connectors or changing wiring. Refrigerant work must be carried out in accordance with applicable regulations and safe-work procedures.

1. Quick fault identification

Indoor receiver LED display

Operation LEDTimer LED3rd LEDFault
Continuous flashContinuous flashOFFModel information error
Continuous flashContinuous flashContinuous flashPower supply frequency error
Continuous flash4 flashes1 flashEEPROM access error
2 flashesContinuous flashOFFRoom temperature thermistor error
3 flashesContinuous flash1 flashHeat exchanger inlet thermistor error
3 flashesContinuous flash2 flashesHeat exchanger middle thermistor error
4 flashesContinuous flashOFFDrain error
5 flashesContinuous flash1 flashStandard wired remote-controller error
5 flashesContinuous flash4 flashesStandard wired token error
6 flashesContinuous flashOFFIndoor fan motor error
Continuous flash5 flashes1 flashSerial signal error
Continuous flash3 flashes3 flashesOutdoor unit error – identify fault at outdoor PCB
Normal indications: In test run, the Operation and Timer lamps flash slowly together. During defrost or oil recovery the indoor fan may stop and the Operation lamp flashes slowly. A power-failure recovery can also produce alternating Operation/Timer indications depending on the auto-restart setting.

Outdoor PCB abnormal display

LED1 flashes rapidly during an outdoor fault. The number of flashes on LED2 to LED5 identifies the fault:

PCB indicationOutdoor faultSection
LED2 × 4Discharge temperature error2.1
LED2 × 7High-pressure error2.2
LED2 × 8Low-pressure error2.3
LED2 × 9Pump-down error – high pressure2.4
LED2 × 10Pump-down error – discharge temperature2.4
LED2 × 11Pump-down error – other2.4
LED3 × 1Discharge thermistor error3
LED3 × 4Heat exchanger liquid thermistor error3
LED3 × 6Heat exchanger middle thermistor error3
LED3 × 10Suction thermistor error3
LED3 × 11Outdoor temperature thermistor error3
LED4 × 1Pressure switch 1 error2.5
LED4 × 2Pressure switch 2 error2.5
LED4 × 4Compressor rotor-location detection error2.6
LED4 × 5Electric current trip2.6
LED4 × 6CT error2.6
LED4 × 9Trip terminal L start-up error2.6
LED5 × 2Power-source frequency abnormal2.7
LED5 × 3EEPROM error2.7
LED5 × 7Microcomputer communication error2.7
LED5 × 8Network communication error5

2. Indoor unit troubleshooting

CodeFaultPrimary checks
E:02Model information errorSupply voltage/noise, connectors, PCB corrosion or damage; replace control PCB if required and restore original address/settings.
E:04Power supply frequency errorCheck supply is 220–240 V, wiring/terminals, voltage drop, outages and electrical noise. Fault detection is below 45 Hz or above 66 Hz.
E:06EEPROM access errorCheck power quality, connectors and control PCB. Replace control PCB if EEPROM access cannot be restored.
E:09Room temperature thermistorCheck connector/cable, thermistor resistance and 5 V PCB sensing circuit.
E:0AHeat exchanger middle thermistorCheck thermistor wiring/resistance and 5 V sensing circuit.
E:0BHeat exchanger inlet thermistorCheck thermistor wiring/resistance and 5 V sensing circuit.
E:11Drain abnormalFloat switch held ON for more than 3 minutes. Check float movement, CN15/wiring and control PCB.
E:13Indoor fan errorCheck fan freedom, shaft/bearing, motor coil, motor temperature, output voltage and fan capacitor where fitted.
E:18Standard wired controller / token errorCheck controller cable and terminals. On applicable ducted units, check CN17 controller supply: approximately DC 12 V indicates controller-side fault; 0 V indicates PCB/supply fault.
E:1FSerial signal errorCheck connection cable, communication PCB/connectors, F401, indoor PCB and power quality. If all indoor units are affected, continue with outdoor network communication checks.

Indoor thermistor reference

ThermistorApproximate resistance
Room temperature0°C 33.6 kΩ; 5°C 25.2 kΩ; 10°C 20.1 kΩ; 15°C 15.8 kΩ; 20°C 12.5 kΩ; 25°C 10.0 kΩ; 30°C 8.0 kΩ; 35°C 6.5 kΩ; 40°C 5.3 kΩ; 45°C 4.3 kΩ; 50°C 3.5 kΩ.
Indoor heat exchanger inlet/middle0°C 176.0 kΩ; 5°C 134.2 kΩ; 10°C 103.3 kΩ; 15°C 80.2 kΩ; 20°C 62.9 kΩ; 25°C 49.6 kΩ; 30°C 39.5 kΩ; 35°C 31.7 kΩ; 40°C 25.6 kΩ; 45°C 20.8 kΩ; 50°C 17.0 kΩ.

3. Outdoor unit troubleshooting

3.1 Discharge temperature error – LED2 × 4

Detection: Compressor stops three or more times after discharge-temperature protection is detected above approximately 118°C within 40 minutes. Protection is released when discharge temperature falls below approximately 93°C.

  • Check refrigerant charge and leaks.
  • Confirm discharge thermistor is correctly mounted and not open/cut.
  • Check SV2 bypass valve and coil.
  • Check outdoor fan and airflow.
  • Check outdoor EEV and EV-KIT operation.
  • Confirm service/3-way valves are fully open.
Leak-test reference from the service material: nitrogen sealing test pressure 600 psi / 4.15 MPa. The source notes that a 5°C ambient change can alter test pressure by about 10 psi / 0.07 MPa.

3.2 High-pressure error – LED2 × 7

Detection: Pressure SW1 opens at high pressure. The source specifies protection at more than approximately 609 psi / 4.2 MPa; repeated detection causes an error.

  • Confirm all service/3-way valves are open.
  • Check Pressure SW1 wiring, connector and switch.
  • Confirm refrigerant charge is correct.
  • Check outdoor fan operation and heat-exchanger airflow.
  • Check outdoor EEV1 and EV-KIT.
  • Check indoor fan operation and filter condition.

3.3 Low-pressure error – LED2 × 8

Detection: Pressure SW2 is detected OFF during compressor operation. Repeated low-pressure protection results in an outdoor fault.

  • Confirm service valves are open.
  • Check for refrigerant shortage/leak and correct charge.
  • Check Pressure SW2 and its wiring.
  • Check EEV1 and EV-KIT.
  • Check outdoor fan and airflow.
  • Check indoor fan/filter condition.
  • Check outdoor-temperature thermistor and its mounting.

3.4 Pump-down errors

IndicationConditionAction
LED2 × 9High-pressure protection during pump downCheck valve position, Pressure SW1, charge, outdoor/indoor airflow, EEV1 and EV-KIT.
LED2 × 10Discharge temperature exceeds approximately 115°C during pump downCheck refrigerant, discharge thermistor, SV2, outdoor fan, EEV1/EV-KIT and gas-side valve position.
LED2 × 11Another protection/error occurs during pump downRelease pump-down mode and operate normally to identify the underlying fault.

The service material notes that pump down may be unrecoverable depending on system refrigerant quantity and ambient conditions.

3.5 Pressure-switch input errors – LED4 × 1 / × 2

These faults are detected when the relevant pressure switch is already open at power-up.

  • Check the relevant switch connector and cable for looseness or damage.
  • Check the switch itself and verify operating pressure.
  • Check the corresponding PCB input circuit for corrosion, damaged tracks or solder faults.
  • Replace the switch or control PCB only after wiring and pressure conditions are verified.

3.6 Compressor, inverter and current-related faults

IndicationFaultKey checks
LED4 × 4Compressor rotor-location detectionCN15/CN16 between control and TR PCB, U/V/W wiring, compressor winding balance, TR PCB output balance and control PCB location-detection circuit.
LED4 × 5Electric current tripElectrical connections, TR PCB/Control PCB, compressor insulation/continuity and balanced U-V/V-W/W-U output.
LED4 × 6CT errorCN202–CN11 wiring, Power PCB CT circuit (source gives approximately 560 Ω at CN11), diode bridge, reactor and TR PCB.
LED4 × 9Trip terminal L start-up errorCN14, TR PCB condition, control PCB IPM supply (approximately 15 V at CN16), trip-terminal circuit and compressor.
Inverter testing: Disconnect power and discharge the DC bus before resistance/continuity testing of the TR/IPM section. When testing a running system, compare U–V, V–W and W–U outputs only using appropriate equipment and procedures.

3.7 Outdoor control / power faults

IndicationFaultChecks
LED5 × 2Power source frequency errorFrequency below 45 Hz or above 65 Hz for more than approximately 1 minute. Check supply, terminals, voltage, cable specification, electrical noise and Power PCB.
LED5 × 3Outdoor EEPROM errorCheck 220–240 V supply, connection cable, voltage drop/noise, all connectors and control PCB condition.
LED5 × 7Microcomputer communication errorCheck supply, cable/terminal integrity, electrical noise and outdoor control PCB. Restore any DIP settings after PCB replacement.

4. Outdoor thermistor checks

For thermistor faults, first inspect the connector and wiring, then disconnect the thermistor and compare resistance with the reference table. If the thermistor is normal, check for approximately DC 5 V at the relevant PCB sensing circuit.

SensorConnectorPart number in sourceLED
Discharge temperatureCN219704219107LED3 × 1
Heat exchanger liquidCN229703306037LED3 × 4
Heat exchanger middleCN249900193010LED3 × 6
Suction temperatureCN259900192013LED3 × 10
Outdoor temperatureCN269900378035LED3 × 11

Discharge thermistor resistance

Temperature °C051015203040506070
Resistance kΩ17613510581.864.541.126.918.112.58.8

Additional discharge reference points: 80°C 6.3 kΩ; 90°C 4.6 kΩ; 100°C 3.4 kΩ; 120°C 2.0 kΩ; 140°C 1.2 kΩ; 160°C 0.8 kΩ; 180°C 0.5 kΩ.

Heat exchanger liquid / middle / suction thermistor resistance

Temperature °C-10-5051015202530
Resistance kΩ27.520.916.112.49.77.76.14.93.9

Outdoor ambient thermistor resistance

Temperature °C-20-10-5051015203040506070
Resistance kΩ10558.244.033.625.920.215.812.58.05.33.62.51.8

5. Network communication error – LED5 × 8

The outdoor unit reports a network communication error when indoor-unit information cannot be received for approximately 20 seconds at start-up or during operation.

Do not branch the interconnection wiring. The source specifically shows branched indoor-unit connections, indoor units connected directly to the commercial supply instead of through the specified system arrangement, and branching from terminal boards as incorrect configurations that can blow fuses.
  1. Check outdoor-to-indoor connection cable polarity and terminal sequence.
  2. Check Outdoor Power PCB communication connector CN201.
  3. Check Outdoor Power PCB terminal TM203 (RED) and fuse F202.
  4. Check each indoor terminal block.
  5. Check indoor Communication PCB wiring and fuse F401.
  6. Complete address setting: power ON → perform each indoor-unit address setting → power OFF → power ON.

6. Remote controller diagnostics

Wired / simple remote controller

If E:EE flashes on the clock display, run self-diagnosis. The service material also provides functions to display the refrigerant-circuit address, indoor-unit address and up to 16 stored error codes.

  • Stop air-conditioner operation before entering diagnostic mode.
  • On the standard wired controller, the source uses the Set Temperature buttons with Start/Stop for address/history access, and a long press of the Set Temperature buttons for self-diagnosis/exit.
  • On the simple controller, self-diagnosis uses Fan Control together with the Set Temperature buttons.
Controller variations: Button combinations differ between controller types. Confirm the controller model before instructing a customer or technician to enter service functions.

Common controller error-code reference

CodeTypical meaning
00No error
02Model information abnormal
04Power supply frequency abnormal
06EEPROM access error
07EEPROM deletion error
09Room temperature thermistor
0AHeat exchanger middle thermistor
0BHeat exchanger inlet thermistor
0CHeat exchanger outlet thermistor
0DBlower temperature thermistor
11Drain abnormal
12Room temperature abnormal
13Indoor unit fan error
18Standard wired remote-controller communication error
1FTransmission error
32 / outdoor error indicationOutdoor unit fault – read outdoor PCB LED pattern for the specific cause.

7. Outdoor PCB normal-operation indicators

The outdoor PCB LEDs also show operating state when no fault is present. LED1 remains lit and LEDs 2–6 indicate conditions including cooling, heating, compressor-frequency range, pressure balance, oil recovery, defrost, test run, pump-down completion, SV1/SV2 open and compressor rotation-speed protection.

Important: A flashing outdoor PCB LED is not automatically a fault. Compare the flash rate and the active LED number with the normal-operation and abnormal-operation tables before replacing components.

8. Recommended diagnostic sequence

  1. Record the indication before resetting power. Capture controller code and indoor/outdoor LED pattern.
  2. Confirm supply and installation. Check voltage, terminals, loose wiring, breaker/cable condition and electrical noise.
  3. Check connectors and harnesses. Look for loose plugs, cut cables, corrosion, damaged tracks and incorrect connections.
  4. Check the sensor or actuator named by the fault. Use the resistance/voltage values above where provided.
  5. Check system conditions. Refrigerant charge, valve position, airflow, EEV operation and operating pressures can create protection faults without an electrical component being defective.
  6. Replace PCB/components only after the upstream checks are completed. Restore original address and DIP-switch settings after PCB replacement.
  7. Run and verify. Confirm normal operation and ensure the error does not recur under load.
Technical information condensed from the J Series troubleshooting service material. Refer to the applicable model service manual and wiring diagram before component replacement or live testing.