J Series Remote Controller Group Setting Mode

DIP switch settings for wired and simple remote controllers
Use these settings when configuring one or two wired remote controllers on the same indoor unit.
Important: Always set the DIP switches before turning the power on. Isolate power before changing any DIP switch position.
Two separate remote controllers can be used to operate the same indoor unit. When two controllers are connected, one controller must be configured as the Master and the other as the Slave.

1. Remote controller master / slave setting

Set DIP SW1 and DIP SW2 according to the number of wired remote controllers connected.

Number of remote controllersMaster unitSlave unit
DIP SW1DIP SW2DIP SW1DIP SW2
1 (Normal) — Factory settingONOFF
2 (Dual)OFFOFFONON
Dual-controller configuration: Set the Master controller to SW1 OFF / SW2 OFF and the Slave controller to SW1 ON / SW2 ON.

2. Other DIP switch functions

DIP SW3 – Setting forbidden

Do not change DIP SW3. The source material identifies this switch as setting forbidden.

DIP SW4 – Model setting

SW4Model setting
OFFHeat Pump — Factory setting
ONCooling only

DIP SW5 – Auto changeover validity

Heat pump models: Never turn SW5 ON on a heat pump model.
SW5Auto changeover
OFFInvalidity — Factory setting
ONValidity

DIP SW6 – Memory backup switch

Set SW6 to ON to use batteries for memory backup. If batteries are not used, stored settings will be deleted if there is a power failure.

Applicability: This function is available for the wired remote controller only. The source material states that this setting is forbidden for the simple remote controller.
SW6Battery backup
OFFInvalidity — Factory setting
ONValidity

3. Quick reference

SwitchFunctionFactory / normal setting
SW1 / SW2Master / Slave controller configurationSingle controller: SW1 ON, SW2 OFF
SW3Setting forbiddenDo not change
SW4Heat pump / cooling-only model selectionOFF = Heat Pump
SW5Auto changeover validityOFF = Invalidity
SW6Battery memory backupOFF = Invalidity
Key setup for two wired controllers:
Master = SW1 OFF / SW2 OFF
Slave = SW1 ON / SW2 ON
Make all DIP switch changes with the system power isolated.