Ducted Unit Connection Dimensions and Static Pressure Reference

Quick reference for compatible indoor and outdoor units, external static pressure ranges, duct connection dimensions and optional connection kits.

Use this guide for:
  • Pre-installation duct sizing and unit selection checks
  • Replacement compatibility assessments
  • External static pressure setup and commissioning
  • Identifying applicable supply and return air connection kits

1. Overview

This reference covers the ARTG, ARTA, ARTC, ARXB, ARXA and ARXC ducted series. It summarises:

  • Available static pressure modes
  • Recommended external static pressure ranges
  • Supply and return air connection dimensions
  • Optional duct connection kits, including UTD-RF204 and UTD-SF045T

Use the information as a field installation and commissioning reference to support correct airflow matching and physical duct sizing.

2. ARTG High Static Ducted - Single Phase

Indoor modelOutdoor modelStatic modesPressure rangeSupply airReturn air
ARTG45LDTAAOTG45LBTA2060-250 Pa1162 x 277 mm1295 x 316 mm
ARTG54LDTAAOTG54LBTA2060-250 Pa1162 x 277 mm1295 x 316 mm
ARTG60LDTAAOTG60LBTA2060-250 Pa1162 x 277 mm1295 x 316 mm
Field application
  • Suitable for high-static commercial duct applications.
  • The available static range supports multiple branch duct layouts and increased filtration resistance.
  • Confirm whether UTD-RF204 and UTD-SF045T are required for the proposed duct transition.

3. ARTC High Static Ducted - Three Phase

Indoor modelOutdoor modelPressure rangeSupply airReturn air
ARTC72LATUAOTA72LALT50-250 Pa1200 x 350 mm1251 x 370 mm
ARTC90LATUAOTA90LALT50-250 Pa1200 x 350 mm1251 x 470 mm
  • Designed for larger commercial multi-room ducted systems.
  • Three-phase supply and static pressure capability up to 250 Pa support longer duct runs.
  • External control features may include Low Noise, Peak Cut and Error Output. Refer to the applicable service documentation.

4. ARTA Slimline Ducted - Single Phase

Indoor modelOutdoor modelPressure rangeSupply airReturn air
ARTA30LBTUAOTA30LBTL30-150 Pa1015 x 240 mm1015 x 240 mm
ARTA45LATUAOTA45LBTL30-150 Pa1015 x 240 mm1015 x 240 mm

These slimline indoor units are intended for restricted ceiling cavities and medium-static applications with comparatively short duct runs.

5. ARTG Bulkhead Ducted Units

Indoor modelOutdoor modelStatic rangeSupply airReturn air
ARTG09LLLBAOTG09LBCA0-90 Pa650 x 151 mmBulkhead
ARTG18LLTAAOTG18LACC0-90 Pa850 x 151 mmBulkhead
Field tip: Confirm condensate drain position and airflow direction against the ceiling cavity layout before installation.

6. VRF and Commercial Series

SeriesUnit typeStatic rangeOptional kits
ARXBVRF bulkhead0-50 PaConfirm by model
ARXAVRF slimline30-150 PaUTD-RF204 / UTD-SF045T
ARXCVRF high static100-300 PaConfirm by model

7. Service and Commissioning Checks

Static pressure tuning
Use the available fan and static pressure settings to calibrate airflow within the recommended range. Measure using appropriate commissioning instruments.
Transition ducts
Confirm the correct return and supply connection kits before adapting to non-standard ductwork. Poor transitions can increase turbulence and reduce delivered airflow.
Replacement systems
Check physical duct dimensions, electrical phase, capacity and external static pressure requirements before selecting a replacement.
Commissioning
Measure external static pressure and confirm the system operates within the applicable range for airflow, capacity and noise performance.

8. Quick Reference Summary

SeriesTypeStatic rangePhaseOptional kits
ARTGHigh static60-250 PaSingleUTD-RF204 / UTD-SF045T
ARTASlimline30-150 PaSingleUTD-RF204 / UTD-SF045T
ARTCHigh static50-250 PaThreeUTD-RF204 / UTD-SF045T
ARXBBulkhead0-50 Pa-Confirm by model
ARXASlimline30-150 Pa-UTD-RF204 / UTD-SF045T
ARXCHigh static100-300 Pa-Confirm by model
Important: This article is a quick reference only. Confirm all model-specific dimensions, connection kits, function settings and commissioning requirements against the applicable installation or design and technical manual before commencing work.